Flame Detection
"Fireye provides a variety of flame scanners which accurately detect the presence or absence of flame in a combustion chamber. Our scanners include advanced sensors and algorithms that can discriminate it's target burner from adjacent flames in the same combustion chamber.
Scanners
 |
|
|
|
45FS1/45UVFS1
|
|
45RM4 |
|
Features: • Patented flame detection method that "learns the signature"of 3 different fuels • Keypad/display for programming or learning flame information • Remote communications capability • Remote file select capability
Specifications: • 45FS1: 700-2,500 nm (IR) • 45UVFS1: 290-390 nm (UV) • Supply voltage: 24 VDC |
|
Features: • 16 position frequency selector switch • Gain adjustment potentiometer • 10 LED flame strength indicator
Specifications: • Lead sulphide detector: 700-2,500 nm • Supply voltage: 24 VDC |
|
|
|
|
45UV5-1000
|
|
45UV5-1009
|
|
Features: • Ultraviolet tube, sensitivity deep in the UV range for improved discrimination • Adjustable sensitivity based on position of UV tube
Specifications: • Optical range: 190-270 nm • Supply voltage: 120 VAC, provided by 25SU3/25SU5 amplifier • Available in NEMA (Class I, Division 2, Group C and D) and Cenelec approved explosion proof housing (EEx d IIC T6) |
|
Specifications: • Self-checking shutter assembly • Optical range: 190-270 nm • Supply voltage: 560 VAC (supplied by control) • Mounting threads: 1" NPT • Operating temp: -40°C to 60°C (-40°F to 140°F) • Available in NEMA (Class 1, Div 2, Group C and D) and Cenelec approved explosion proof housing (EEx d IIC T6)
|
|